| Section 10 offers suggestions for troubleshooting hardware problems. If these suggestions do not solve your problem or if you encounter a problem that is not listed here, contact Silent Knight Technical Support at 800-328-0103 for assistance. |
Common Problems
|
Problem
|
Possible
Cause / Suggested Action(s)
|
|
Trouble
message "DBL ADDR" (Doble Address) displays on LCD.
|
An
address has been assigned to more than one detector. Find the duplicate
address SLC device and correct the address.
|
If the location of the duplicate address is unknown, use the SLC Device Locator function to locate it. The SLC Device Locator function was described in section 8 under Point Functions Main Menu option. Once the SLC Device Locator function has been activated, walk the SLC loop to find the two or more detectors that are flashing.

![]() |
![]() |
![]() |
|