Page
1 of 10
|
| Section 5 describes the installation and addressing of the 5808 Fire Alarm Control Panel's SLC (Signaling Line Circuit) devices. |
|
WARNING!
|
|
To
avoid the risk of electrical shock and damage to the unit, power sould
be OFF at the control panel while installing or servicing.
|
Types of SLC Devices
The following types of SLC devices can be used with the system.
|
Model
#
|
Description
|
|
|
Model
SD500-AIM
|
Input
Module (switch input), standard size, dipswitch configurable.
|
|
|
Model
SD500-LED
|
Addressable
LED Driver Module. Capable of driving 80 LEDs. Up to 40 SD500-LED modules
can be used on the SLC loop.
|
|
|
Model
SD500-MIM
|
Mini
Input Monitor Module (switch input), small size, dipswitch configurable.
Fits in single-gang box with manual pull station switch.
|
|
|
Model
SD500-ARM
|
Addressable
Relay Module, dipswitch configurable.
|
|
| Model SD505-AHS | Heat Sensor |
|
|
Model
SD505-AIS
|
Ionization
Smoke Detector
|
|
|
Model
SD505-APS
|
Photoelectric
Smoke Detector
|
|
|
Model
SD505-ADH
|
Duct
Housing (Used with SD505-AIS or SD505-APS smoke detectors).
|
|
|
Model
SD505-ADHR
|
Duct
Detector Housing with Relay (Used with SD505-AIS or SD505-APS smoke
detectors).
|
|
|
Model
SD505-DTS
|
Remote
Test Switch & LED indicator for the SD505-ADHR.
|
|
|
Model
SD500-PS
|
Addressable
Pull Station.
|
|
|
Model
SD500-LIM
|
SLC
short circuit isolator module. Fits in a double gang box.
|
|
|
Model
SD505-6IB
|
Short
circuit isolator base for SD505-AHS, SD505-AIS, and SD505-APS SLC devices.
|
|
![]() |
![]() |
![]() |
|
Page