JumpStart Autoprogramming Input Points
JumpStart will determine the number and type of input points (detectors or contact monitor modules) on each SLC loop. JumpStart assigns the correct detector type (heat or photoelectric), so the installer does not need to edit device type for detectors. Any contact monitor modules on the system will be assigned type "Manual Pull". The installer will need to manually change the switch type if manual pull is not correct.
JumpStart creates one zone (Zone 1) and assigns all input points to Zone 1. Zone 1 is mapped to Output Group 1. After JumpStart completes, you can re-map to configure a multiple zone/output group system.
JumpStart Autoprogramming Output Points
JumpStart creates three output groups and assigns output circuits as follows:
Circuits
1 - 4:
Configured as Notification and assigned to Group 1. JumpStart automatically
programs Zone 1 to activate Group 1 using constant on output.
Circuit 5
(Relay 1):
Assigned to Group 124.
JumpStart automatically programs Zone 1 to activate Group 124 using constant
on output when a supervisory condition occurs.
Circuit 6
(Relay 2):
Assigned to Group 125. JumpStart automatically programs Zone 1 to activate
Group 125 using constant on output when an alarm occurs.
Addressable
Relay Modules:
All addressable relay modules will be configured as "Output Pt"
(general purpose output point) and assigned to Group 1.
|
NOTE
|
Relay output is constant even if the zone activating the relay is programmed with an output pattern. |
![]() |
![]() |
|
|