Section 3 - System Overview
 
Page 1 of 5
 

Section 3 describes the 5499 Power Distribution Module terminals and their respective electrical ratings. Section 3 also gives a general explanation of input and output configurations.

Terminal Block Overview

Use the table and drawings below to become familiar with the terminal layout, description, and ratings. Advance through the section for further detail and explanation of input and output configurations.

CAUTION
Each output circuit is rated at 3 amps. DO NOT OVERLOAD. Overloading a circuit wil cause it to shut down (power limit). The circuit will automatically reset once you remove the overload condition.

TB1
TB2

 

Terminal #
Description
Ratings
TB1
1
AC (black - "hot") 120 VAC 60Hz
2
Earth Ground
3
AC (white - "neutral")
TB2
1
Auxiliary Power (-) 24 VDC 3.0 amps
2
Auxiliary Power (+)
3
Notification 4 Output (-) 24 VDC 3.0 amps
4
Notification 4 Output (+)
5
Notification 3 Output (-) 24 VDC 3.0 amps
6
Notification 3 Output (+)
7
Notification 2 Output (-) 24 VDC 3.0 amps
8
Notification 2 Output (+)
9
Notification 1 Output (-) 24 VDC 3.0 amps
10
Notification 1 Output (+)
11
Normally Closed Contact 2.5 A @ 30 VDC
12
Common
13
Normally Open Contact
14
Input 2 9 - 30 VDC
15
Input 2 (-)
16
Input 2 (+)
17
Input 1 9 - 30 VDC
18
Input 1 (-)
19
Input 1 (+)

Even though each output is rated for 3 amps, the total current draw from the 4 outputs and the auxiliary power must not exceed 9 amps of notification power.


 