Page
1 of 3
|
The SK-5208 can transmit information in four different formats. Of these four formats some of the formats offer a more specific selection for that format. For example, you can select a 3/1 format that requires a 1400 or 2300 Hz handshake, or SIA format that can handle 8 or 20 events per call. Selecting the correct format depends on the type of receiver that will receive calls from the SK-5208.
The SK-5208 DACT is compatible with the Silent Knight Model 9800 and 9500 Digital Receivers.
Reporting Formats
|
Format
Name
|
Description
|
|
|
Category
Name |
Programming
Name |
|
|
3/1
|
3/1
14
|
Old
format, transmits a 3-digit account number and a 1-digit event code.
Transmissions are acknowledged at 1400 Hz.
|
|
3/1
23
|
Old
format, transmits a 3-digit account number and a 1-digit event code.
Transmissions are acknowledged at 2300 Hz.
|
|
|
4/2
|
SK4/2
1400
|
Tone
burst format, transmits a 4-digit account code and 2-digit event code.
Transmissions are acknowledged at 1400 Hz.
|
|
SIA
|
SIA8
|
Security
Industry Association standard communication format which send a maximum
of 8 events per call. Up to a 6-digit account number.
|
|
SIA20
|
Security
Industry Association standard communication format which send a maximum
of 20 events per call. Up to a 6-digit account number.
|
|
|
Contact
ID
|
Contact
ID
|
Ademco
Contact ID format. DTMF (Dual Tone Multiple Frequency) format. Send
a 4-digit account number. Transmission is acknowledged at both 1400
and 2300 Hz.
|
![]() |
![]() |
![]() |
|
Page