5230 Display Messages
If the 5104 is not reporting, being programmed, and if no functions are being entered, the LCD cycles through all system messages applicable at the time. The display will show a different message every 2 seconds if there is more than one message.

5230 LCD Messages and Meanings
|
Message
|
Meaning
|
|
Trouble
Zone # (1-6)
|
Trouble
condition exist on the zone or zones indicated by #.
|
|
Alarm
Zone # (1-6)
|
Alarm
condition exist on the zone or zones indicated by #.
|
|
Low
AC
|
AC
power has been lost.
|
|
Trouble
Line 1
|
Trouble
condition on phone line 1.
|
|
Trouble
Line 2
|
Trouble
condition on phone line 2.
|
|
Dialer
Trouble
|
Indicates
a dialer failed condition.
|
|
Earth
Ground Fault
|
Indicates
that an earth ground fault condition exists.
|
|
Earth
Pwr Fault
|
Indicates
that an earth ground to power, fault condition exists.
|
|
Silenced
|
A
trouble condition exists and the annunciaton has been turned off.
|
|
System
Normal
|
Displayed
if no trouble, alarm or 5230 system error exists.
|
|
Data
Lost
|
Displayed
if event memory overflows.
|
|
Reporting
|
A
report is being transmitted to central station.
|
|
Up/Download
|
Data
is being uploaded or downloaded from the central station computer.
|
|
Bus
Trouble
|
The
5230 cannot communicate with 5104.
|
|
Try
Again
|
If
there is a 10 seconds time lapse between key presses while entering
a function, the 5230 will display this message. An invalid entry was
made.
|
|
Trouble
Remote # (1-3)
|
One
or more 5230 annunciators are in trouble. The 5230 ID number is indicated
in the # place.
|
|
EEPROM
Sum Error
|
Error
during program mode.
|
|
Low
Battery
|
Battery
voltage is less than 10.2 VDC.
|
|
Trouble
Smk Pwr
|
Smoke
loop power is less than 10 V or an overcurrent condition exists.
|
|
Bell
Trouble
|
Trouble
condition on the notification circuit.
|
|
Trouble
Com 1
|
Auto
test or manual test unable to report on line 1
|
|
Trouble
Com 2
|
Auto
test or manual test unable to report on line 2.
|
|
Supervisory
# (1-6)
|
Alarm
condition on the zone programmed as the sprinkler zone.
|
![]() |
![]() |
![]() |
|